Analysis of wind time-varying performance of reinforced concrete electric pole under Marine atmospheric environment
DOI:
https://doi.org/10.54097/hset.v77i.14360Keywords:
concrete pole, naval air environment, wind-resistant performance, Time-varying performance, failure mode.Abstract
Bearing capacity calculation model of concrete electric pole considering concrete long-term performance degradation and steel corrosion is established. The horizontal bearing capacity and wind resistance of typical concrete electric pole under Marine atmospheric environment are analyzed with service time. The effects of concrete protective layer thickness, stirrup diameter and strength coefficient on the long-term wind resistance of electric pole are discussed. It is found that with the increase of service time, the shear strength of the concrete pole deteriorates faster than that of the flexural strength, and the failure mode changes from bending failure to shear failure. The wind resistance of the pole after long service can be improved by increasing the thickness of the protective layer, adopting larger diameter stirrup and higher strength coefficient. The bearing capacity calculation model of concrete electric pole considering concrete long-term performance degradation and steel corrosion is established. The horizontal bearing capacity and wind resistance of typical concrete electric pole under Marine atmospheric environment are analyzed with service time. The effects of concrete protective layer thickness, stirrup diameter and strength coefficient on the long-term wind resistance of electric pole are discussed. It is found that with the increase of service time, the shear strength of the concrete pole deteriorates faster than that of the flexural strength, and the failure mode changes from bending failure to shear failure. The wind resistance of the pole after long service can be improved by increasing the thickness of the protective layer, adopting larger diameter stirrup and higher strength coefficient.
Downloads
References
Zhi Zhibao. Analysis of the causes of tipping and breaking of a large number of distribution line poles under Typhoon Rammasun [J]. Guangxi Electric Power, 2015, 38 (3): 30-33.
Chen Bin, YU Jilai. Grid-based Evaluation of distribution Network rod failure probability under Strong Typhoon environment [J]. Electric Power Grid, 2018, 37 (16): 42-47.
Liu Yufeng, Wu Haijun, Yi Tao. Analysis of Force of Typhoon Gust Characteristic on pole failure of Distribution Line [J]. Structural Engineer, 2021, 37 (6): 114-121.
Li Feng, XIA Kaiquan, ZHANG Zifu. Research on bearing capacity of concrete pole with Defects [J]. Northeast Electric Power Technology, 2006, (9): 17-19.
Wang Yanhai, Zhang Lu, in. Research on fracture treatment and detection technology of buried deep section of concrete electric pole [J]. Concrete and Cement Products, 2013, (7): 30-32.
Xiong Liang, Wan Keyang, LIU Jiajiao, Cao Zhi. Analysis of fracture causes of reinforced concrete electric pole. Physical and Chemical Test - Physics Branch, 2017, 53 (11): 826-828.
Xiong Yu, Pan Xing, Feng Botao, Tian Ze. Fracture analysis of ring concrete pole in a certain area [J]. Hubei Electric Power, 2022, 46 (3): 122-126.
Zhao Demin. Research on corrosion mechanism of steel bar of Concrete electric pole [J]. Architecture, 2014, (18): 89-90.
Zeng Xian-Le, XU Fei, XIA Kai-Quan. Research on flexural bearing Capacity of Extended Service Reinforced Concrete Pole [J]. Guangxi Electric Power, 2010, 33 (6): 1-4.
Standards for durability of concrete structures: CECS 220: 2007 [S]. Beijing: China Architecture and Building Press, 2007. (in Chinese)
Saetta A V, Scotta R V, Vitaliani R V. Analysis of chloride diffusion into partially saturated concrete [J]. ACI Materials Journal, 1993, 90(5): 441-451.
Ye Zhiwen, Zhang Weiping, Gu Xianglin. Time-varying behavior of reinforced concrete beams in Marine atmosphere [J]. Journal of Building Structures, 2019, 40 (1): 74-81.
Liu T, Weyers R W. Modeling the dynamic corrosion process in chloride contaminated concrete structures [J]. Cement and Concrete Research, 1998, 28(3): 365-379.
Jiang Zi, Wang Qiang. The concrete resistivity calculation model based on microenvironmental impact. Concrete and cement products, 2014 (12): 19-22.
Lu Chunhua, Wang Jian, Cheng Pu. Experimental and numerical simulation of mechanical properties of naturally corroded steel bars in concrete [J] Journal of Jiangsu University of Science and Technology, 2019, 33 (6): 107-113.
Wu Qing, Yuan Yingshu Experimental study on the degradation law of mechanical properties of corroded steel bars Journal of Civil Engineering, 2008, 41 (12): 42-47+3.
Niu Ditao. Changing models of concrete strength along with time in marine environment. Journal of Xi’an University of Architecture and Technology, 1995, 27(1): 49-52.
Chen Xianghe, Liu Zaiguo, Xiao Qi Transmission Tower and Foundation Design (Third Edition) [M] Beijing: China Electric Power Press, 2020.
Ring concrete pole: GB/T 4623-2006 [S] Beijing: China standard press, 2006.
The design specification of concrete structure: GB50010-2010 [s]. Beijing: China construction industry press, 2016.